Advanced Automatic IG55 Inert Gas Fire Suppression System
Description:
IG-55 is a gas composed of an equal combination of two elements: 50% argon and 50% nitrogen. These elements occur naturally in the environment, making IG-55 environmentally friendly as it has no impact on global warming and does not harm the ozone layer.
IG-55 has a density similar to that of air, and both argon and nitrogen are clean, colorless, and odorless gases that are non-corrosive. This makes IG-55 highly adaptable to various actuation systems, as it can be safely used with materials such as nickel, steel, stainless steel, copper, bronze, tin, and others at normal temperatures.
Storage for IG-55 is similar to that of compressed gas, where it is contained in high-pressure cylinders. The space required for storage will depend on the pressure and capacity of the cylinders. Our IG-55 system is designed to operate at a pressure of 30MPa, enabling us to achieve efficient use of storage space.
Technical parameters of IG55 fire suppression system
|
Working temperature (℃) |
0℃~+50℃ |
||
|
Working pressure |
Storage pressure |
20.0MPa |
30.0MPa |
|
Max. working pressure (+50℃) |
23.2MPa |
36.6MPa |
|
|
Min. working pressure (-20℃) |
18MPa |
27MPa |
|
|
Container volume (L) |
80L |
140L |
|
|
Filling weight (kg, @200 bar) |
22.32kg |
39.06kg |
|
|
Filling weight (kg, @300 bar) |
33.48 kg |
58.59kg |
|
|
System operating voltage |
220V AC,24V DC |
||
|
System start mode |
Electrical automatic, electrical manual, mechanical emergency start |
||
|
Design concentration |
Class A dangerous material surface fire |
40.3% |
|
|
Class B |
47.6% |
||
|
The design concentration of the protective zone with people working |
40.3%~43% |
||
Storage cylinder group, storage cylinder group frame, nitrogen driving device, nitrogen driving device frame, the cylinder valve, liquid flow check valve, air flow check valve, electromagnetic starter, gas conveying pipeline, collecting pipe, choice valve, three links, reducer tee, reducing elbow, flange, safety valve, pressure transmitter, pipe, nozzle, chemicals, fire detector, fire controller, sound and light alarm, alarm bell, gas light, emergency start / stop button, etc.
-- Clean and Non-Residue
-- Environmentally Friendly
-- Safe for Occupants
-- Effective Fire Suppression
-- Non-Conductive
1. Data Centers and Server Rooms: Protects sensitive electronic equipment without causing damage.
2. Archives and Libraries: Safeguards valuable documents and artifacts.
3. Telecommunication Facilities: Ensures uninterrupted operations during fire incidents.
4. Museums and Cultural Heritage Sites: Preserves irreplaceable items.
5. Power Generation Facilities: Protects critical infrastructure.